Section 5
5.1
TECHNICAL CHARACTERISTICS
Functional Specifications
Inputs
See table 1, 2 and 3
Communication
Protocol
Digital only. Complies with IEC 61158-2: 2000 (H1): 31.25 kbit/s voltage mode, bus powered.
Current
Consumption
Bus powered: 9 - 32 Vdc.
Quiescent current consumption: 14 mA.
Failure Alarm
For sensor or circuit failures, status is sent to output parameters. Detailed diagnostics are available in the contained
parameters.
Temperature Limits
Operation:
Storage:
0 ºC to 75 ºC
0 ºC to 85 ºC
(32 ºF to 167 ºF)
(32 ºF to 185 ºF)
Performs within specifications in less than 12 seconds after power is applied to the transmitter.
Configuration
Remote configuration using Profibus PA protocol, with AMSTM, FieldCareTM, HHT375, Profibus View or Simatic PDM.
Humidity Limits
0 to 75 RH
Performance Specifications
Accuracy
See tables 1, 2 and 3
Ambient
Temperature
Effect
mV (- 6 to 22 mV), TC (NBS: B, R, S,T): ± 0.03% of the input milivoltage or 0.002 mV whichever is greater;
mV (- 10 to 100 mV), TC (NBS: E, J, K, N; DIN: L, U): ± 0.03% of the input milivoltage or 0.01 mV whichever is greater;
mV (-50 to 500 mV): ± 0.03% of the input milivoltage or 0.05 mV whichever is greater;
Ohms (0 to 100 Ω), RTD (GE: Cu10): ± 0.03% of the input resistance or 0.01 Ω whichever is greater;
Ohms (0 to 400 Ω), RTD (DIN: Ni120; IEC: Pt50, Pt100; JIS: Pt50, Pt100): ± 0.03% of the input resistance or 0.04 Ω
whichever is greater;
Ohms (0 to 2000 Ω), RTD (IEC: Pt500), RTD (IEC: Pt1000): ± 0.03% of the input resistance or 0.2 Ω whichever is
greater;
TC: cold-junction compensation rejection 60:1 (Reference: 25.0 ± 0.3 °C).
Effect
± 0.005% of calibrated span per volt.
Interference
Approved according to
IEC 61000-6-2:1999, IEC 61000-6-4:1997 and IEC 61326:2002.
Physical Specifications
Housing
Housing profile are made of Anodized Aluminum. Lateral caps are made of PA 6.6
Terminal Block
1 terminal for power supply connection;
8 terminals for sensor connection.
Weight
300 g
Using DIN rail EM 60715 (previously DIN EN 50022).
Housing
Protection: IP20
Functions
Characteristics
Physical Block, Tranducer and Analog Input.