Section 3
3.1
CONFIGURATION
This section describes the TT383 blocks. They follow the Profibus PA specifications, but concerning
the transducer blocks, the input transducer block and display, they have some special features. The
303 Smar family is integrated in Profibus View, from Smar and in the Simatic PDM, from Siemens.
It is possible to integrate any Smar device in Profibus with any configuration tool for Profibus PA
devices. It is necessary to provide a Device Description or Drive according to the configuration tool.
In this manual it is possible to find some examples using Profibus View or Simatic PDM.
In order to assure correct values in the offline configuration, first run “Download to PG/PC” option to
assure valid values. After, run the Menu Device option to configure the required parameters using
the related menus.
NOTE
In offline configuration, it is not recommendable to use the “Download to Device” option. This
function can misconfigure the equipment.
Transducer Block
Transducer block insulates function blocks from the specific I/O hardware, such as sensors,
actuators. Transducer block controls access to I/O through manufacturer specific implementation.
This allows the transducer block to execute as frequently as necessary to obtain good data from
sensors without burdening the function blocks that uses the data. It also insulates the function block
from the manufacturer specific characteristics of certain hardware.
By accessing the hardware, the transducer block can get data from I/O or passing control data to it.
The connection between Transducer block and Function block is called channel. These blocks can
exchange data from its interface.
Normally, transducer blocks perform functions, such as linearization, characterization, temperature
compensation, control and exchange data to hardware.
How to Configure a Transducer Block
The transducer block has an algorithm which is a set of contained parameters. It means that it is no
possible to link these parameters to other blocks and publish this link via communication and a
channel connecting it to a function block.
The algorithm describes the behavior of the transducer as a data transfer function between the I/O
hardware and other function block. The transducer parameter cannot be linked in input and output of
others blocks.
The transducer parameters can be divided in manufacturers’ standard and specific parameters.
The standard parameters will be present for such class of device, as pressure, temperature,
actuator, etc., whatever is the manufacturer. Oppositely, the manufacturers specific ones are
defined only for its manufacturer. As common manufacturer specific parameters, we have calibration
settings, material information, linearization curve, etc.
When you perform a standard routine such as calibration, you are guided step by step by a method.
The method is generally defined as guideline to help the user to make common tasks. The
Configuration Tool identifies each method associated to the parameters and enables the interface to
it.